Aqua Environmental Leak Detection  located a water leak in a 600mm ductive iron concrete lined water main recently installed on a NSW water project. The new section of pipeline was 1700m long and failing a final pressure test prior to commissioning, the leak was estimated to be 100 litres per half an hour.

Aqua Environmental Leak Detection determined that one valve was broken, and then focussed on a particular section of a main that was 700m long. After deploying a large diameter leak detection correlator, Aqua Environmental Leak Detection got a better reading on the first correlation and marked the site for excavation.

Aqua Environmental Leak Detection excavated the site and a leaking gibault was located on the water main at the exact location they had marked. This leak was located and repaired quickly.